VMC Double Flux Eurovent - Échangeurs rotatifs
Internal Leakage class
C3
Percentage Internal Leakage
3.99 %
External Leakage class
C3
Percentage External Leakage
1.99 %
Airflow-pressure certified window
ptUd
100
qv max
0.2240 m³/s
ptUD/2
50
qv ref
0.1570 m³/s
Pe ref
139.00 W
SPI
0.25 W/(m³/h)
Temp. Ratio
85.90 %-point
Lw casing
40 dB(A)
Lw supply
61 dB(A)
Lw extract
52 dB(A)
Lw exhaust
61 dB(A)
Lw outdoor
52 dB(A)
SEC
-42.80 kWh/m².a
SEC Class
A+
AEC
132.00 kWh/annum
AHS Average
4609.00 kWh/annum
AHS Cold
9015.00 kWh/annum
AHS Warm
2084.00 kWh/annum
MISC
1.10
CTRL
0.65
x-value
2.00
Filter class supply
ISO ePM1 50%
Filter class exhaust
ISO ePM1 50%