VMC Double Flux Eurovent - Échangeurs rotatifs

Model HERU 95 T EC-y1 ALC

Gamme

HERU

N° de diplôme

22.04.008

Participant

2057

Brand

Östberg

Internal Leakage class

C3

Percentage Internal Leakage

3.99 %

External Leakage class

C3

Percentage External Leakage

1.99 %

Airflow-pressure certified window

Download file

ptUd

100

qv max

0.0990 m³/s

ptUD/2

50

qv ref

0.0700 m³/s

Pe ref

114.00 W

SPI

0.46 W/(m³/h)

Temp. Ratio

85.00 %-point

Lw casing

43 dB(A)

Lw supply

75 dB(A)

Lw extract

59 dB(A)

Lw exhaust

75 dB(A)

Lw outdoor

59 dB(A)

SEC

-39.80 kWh/m².a

SEC Class

A

AEC

243.00 kWh/annum

AHS Average

4590.00 kWh/annum

AHS Cold

8979.00 kWh/annum

AHS Warm

2075.00 kWh/annum

MISC

1.10

CTRL

0.65

x-value

2.00

Filter class supply

ISO ePM1 50%

Filter class exhaust

ISO ePM1 50%