Residential ventilation Eurovent - Rotary heat exchangers

Model HERU 100 S EC-y1

Rango

HERU

Número de diploma

22.04.008

Participant

2057

Brand

Östberg

Internal Leakage class

C3

Percentage Internal Leakage

3.99 %

External Leakage class

C3

Percentage External Leakage

1.99 %

Airflow-pressure certified window

Download file

ptUd

100

qv max

0.1080 m³/s

ptUD/2

50

qv ref

0.0760 m³/s

Pe ref

104.00 W

SPI

0.38 W/(m³/h)

Temp. Ratio

84.40 %-point

Lw casing

43 dB(A)

Lw supply

72 dB(A)

Lw extract

60 dB(A)

Lw exhaust

72 dB(A)

Lw outdoor

60 dB(A)

SEC

-40.70 kWh/m².a

SEC Class

A

AEC

201.00 kWh/annum

AHS Average

4577.00 kWh/annum

AHS Cold

8955.00 kWh/annum

AHS Warm

2070.00 kWh/annum

MISC

1.10

CTRL

0.65

x-value

2.00

Filter class supply

ISO ePM1 65%

Filter class exhaust

ISO ePM1 65%