Residential ventilation Eurovent - Rotary heat exchangers

Model HERU 70 K EC -y1 R

Gamma

HERU

Diploma

22.04.008

Participant

2057

Brand

Östberg

Internal Leakage class

C3

Percentage Internal Leakage

3.99 %

External Leakage class

C3

Percentage External Leakage

1.99 %

Airflow-pressure certified window

Download file

ptUd

100

qv max

0.0890 m³/s

ptUD/2

50

qv ref

0.0570 m³/s

Pe ref

109.00 W

SPI

0.53 W/(m³/h)

Temp. Ratio

80.00 %-point

Lw casing

44 dB(A)

Lw supply

70 dB(A)

Lw extract

56 dB(A)

Lw exhaust

70 dB(A)

Lw outdoor

56 dB(A)

SEC

-37.90 kWh/m².a

SEC Class

A

AEC

281.00 kWh/annum

AHS Average

4486.00 kWh/annum

AHS Cold

8776.00 kWh/annum

AHS Warm

2029.00 kWh/annum

MISC

1.10

CTRL

0.65

x-value

2.00

Filter class supply

ISO ePM1 50%

Filter class exhaust

ISO ePM1 50%