Residential ventilation Eurovent - Rotary heat exchangers

Model HERU 200 S EC-y1

Диапазон

HERU

Номер диплома

22.04.008

Participant

2057

Brand

Östberg

Internal Leakage class

C3

Percentage Internal Leakage

3.99 %

External Leakage class

C3

Percentage External Leakage

1.99 %

Airflow-pressure certified window

Download file

ptUd

100

qv max

0.2180 m³/s

ptUD/2

50

qv ref

0.1530 m³/s

Pe ref

142.00 W

SPI

0.26 W/(m³/h)

Temp. Ratio

85.90 %-point

Lw casing

42 dB(A)

Lw supply

70 dB(A)

Lw extract

58 dB(A)

Lw exhaust

70 dB(A)

Lw outdoor

58 dB(A)

SEC

-42.60 kWh/m².a

SEC Class

A+

AEC

138.00 kWh/annum

AHS Average

4609.00 kWh/annum

AHS Cold

9015.00 kWh/annum

AHS Warm

2084.00 kWh/annum

MISC

1.10

CTRL

0.65

x-value

2.00

Filter class supply

ISO ePM1 65%

Filter class exhaust

ISO ePM1 65%